Energy Link

Energy Link is the Thunder communication link used between compatible Thunder devices. It carries both 54 VDC power and network communication over the same two conductors (ELL and ELH), allowing power and data to share a single twisted pair.

Energy Link uses the ELL and ELH conductors to carry both 54 VDC power and network communication between Thunder devices. A shield connection is also used where specified by the product wiring diagram.

Connection

Description

ELH

Energy Link High

ELL

Energy Link Low

Shield

Connect the cable shield to the Shield terminal when required by the product wiring diagram.

Cabling Requirements

Parameter

Requirement

Voltage

54 VDC

Cable

Single twisted pair

Wire gauge

18 or 20 AWG, depending on the connected product specification

Maximum distance

1000 m (3280 ft)

Shield

Connect where indicated by the product wiring diagram

Energy Link is used to connect Thunder cabin phones to the Thunder system.

  • Low-Rise systems: TG1132 and TG1164 supervisors provide Energy Link ports for the Thunder cabin phones.

  • High-Rise systems: The TP1002 connects to TG1232 and TG1264 gateways through Energy Link. Each gateway then provides Cabin connections for the Thunder cabin phones using ELL, ELH, and Shield.

For complete system wiring, refer to the installation documentation for the applicable Thunder architecture.